High-pressure angle type control valve (electric)
Technical Specifications
Product model: ZDLS, ZAZS
Nominal diameter: DN20 - 300mm
Nominal pressure: PN1.6 - 32 MPa
Valve structure: 90° right-angle type
Flow characteristics: Linear, Equal Percentage
Valve core type: Sleeve-guided single-seat piston type valve core
Operation switch: PSL, 3810 (electric open type, electric close type)
Operating temperature: General type -40 to 230℃; Fin type 230 to 450℃
Adjustable coefficient: When the Kv value is less than 18, R = 20:1; when the Kv value is 18 or above, R = 30:1.
European standard: Compliant with JB/T2769-92 standard. Orders can be placed according to ANSI, JIS, DIN, etc. for production.
Sales Hotline:
Product Details
Product Overview
The electric high-pressure angle type regulating valve adopts a top-guided structure. It is composed of an angle-type regulating valve body combined with a 3810L type (or PSL series) linear electronic electric actuator. The actuator contains a servo function and accepts a unified 4-20mA or 1-5V·DC standard signal. It converts the current signal into the corresponding linear displacement, automatically controlling the opening degree of the electric angle-type regulating valve, and achieving continuous regulation of process parameters such as pressure, flow, temperature, and liquid level in the pipeline. It has the characteristics of sensitive operation, simple wiring, large flow rate, small size, and high regulation accuracy. The valve body is of a right-angle shape, the valve core is of a single-guided structure, the valve body flow path is simple, and the resistance is small. It is particularly suitable for the regulation of high-viscosity, suspended matter-containing, and particle-like medium fluids. It can avoid coking, blockage, and is also convenient for self-cleaning and water cleaning. Electric high-pressure angle type regulating valves are generally used in bottom-in and side-out situations, as this can ensure better stability in regulation.
Main purpose
The electric high-pressure angle regulating valve is a product developed specifically for regulating valves under harsh working conditions such as high pressure or high pressure difference, severe cavitation and erosion. It adopts a multi-stage throttling method to distribute the pressure difference, reducing cavitation, erosion, and flow distortion damage, thereby significantly increasing the service life of the regulating valve. In particular, when used in the urea system, its service life is 2-3 times longer than that of ordinary high-pressure valves.
Main external connection dimensions
| (DN) | 20 | 25 | 32 | 40 | 50 | 65 | 80 | 100 | 125 | 150 | 200 | 250 | 300 | |
| L、L1 | PN16/25 | 95 | 100 | 105 | 115 | 125 | 145 | 155 | 175 | 200 | 225 | 275 | 95 | 100 |
| PN40 | 95 | 100 | 105 | 115 | 125 | 145 | 155 | 175 | 200 | 225 | 275 | 95 | 100 | |
| PN64 | 115 | 115 | 130 | 130 | 150 | 170 | 190 | 215 | 250 | 275 | 325 | 115 | 115 | |
| H | PN16/25 | 119 | 119 | 122 | 140 | 157 | 169 | 179 | 200 | 230 | 250 | 304 | 365 | 420 |
| PN40 | 123 | 123 | 134 | 152 | 157 | 191 | 201 | 216 | 240 | 270 | 325 | 380 | 400 | |
| PN64 | 135 | 135 | 142 | 160 | 177 | 196 | 206 | 227 | 257 | 277 | 331 | 410 | 430 | |
| H1 | 3810L | 373 | 373 | 495 | 495 | 495 | 700 | 700 | 700 | 725 | 725 | 725 | 725 | 725 |
| PSL | 465 | 465 | 465 | 465 | 465 | 560 | 560 | 560 | 560 | 560 | 788 | 788 | 788 | |
| D | 3810L | 225 | 225 | 225 | 225 | 225 | 257 | 257 | 257 | 310 | 310 | 310 | 310 | 310 |
| PSL | 177 | 177 | 177 | 177 | 177 | 182 | 182 | 182 | 182 | 182 | 218 | 218 | 218 | |